BRAND | Loreme |
Product | IPL50/CM |
Description | INDICATOR FOR ELECTRICAL MEASUREMENTS |
Internal code | ONR4014053 |
Custom code | 90308930 |
Technical specification | Configurable measurements - DC measurement: voltage, current, power - AC measurement: voltage, current - Frequency, cos phi, active, reactive, apparent power - Single-phase, three-phase balanced network, with or without neutral - Configurable IT and TP report Available inputs - Voltage 0 ... 125 Vac, +/- 175 Vdc or - Voltage 0 ... 500 Vac, +/- 700 Vdc - Current 0 ... 1 Aac, +/- 1 Adc or - Current 0 ... 5 Aac, +/- 5 Adc - Frequency: 40 ... 400 Hz - Use : * Voltage: 125 Vdc * Current: 100 mVdc * Frequency: / Configurable relay - 2 changeover relays, potential free contacts Option (IPL50 / A) - “Special Alarm” Pack - Low, high, internal window, external alarms - Memorization of alarm states - Alarm delay - Alarm validation condition - Positive or negative relay safety Display - 4 digits LED 7 segments, 10,000 points - Measurement display, fixed, scrolling, setting alarm thresholds Power supply - 20 ... 70 Vac / dc or 80 ... 265 Vac / dc - Use: 125 Vdc (To be confirmed) Insulation - Power supply / inputs / relay 1500Vac Configuration - USB link (Cord supplied separately) Communication option / CM - 2-wire RS485, Modbus protocol |
Press on flag images to see contact information!