BRAND | BFI AUTOMATION |
Product | flame scanner 2.0GT |
Description | flame scanner |
Internal code | IMP4444220 |
Custom code | 84169000 |
Technical specification | designed to detect flames on gas turbines and provides fmale information to a BFI flame amplifier. equipped with a amultiple-semi-conductor sensort and covers the spectral range from UV to IR. Separate sensitivity adjustment for UV and IR range. Automatic Gain and Frequency Control (AGC & AFC) spectral range 300 -2700nm operating mode continuous operation viewing angle 2.7 self checking once per second supply voltage 24V DC current consumption approx.200mA ambient temperature -20c to +70c cable conntection harting plug 90 dimensions mm L 235 x W 108 x H 108 housing aluminium, ral5010, IP 65 Atex Zone 2 II 3 G nA IIC T4 Gc X gain control automatic AGC frequency control automatic AFC SIL Cerification SIL3 in combination with flame amplifier 3001, 3001D, 3001S |
default.send_request_amp_Group2