Prices  VLC-600  Simplex  United States

BRAND Simplex
Product VLC-600
Description TrueAlarm LaserCOMPACT Smoke Sensor
Internal code IMP3778277
Weight 1.9
Technical specification (sampling pipe is ordered separately) 2098-9808 - Remote Red LED Status Indicator on single gang stainless steel plate; mounting requires a single gang box, 1 ½” minimum depth; connections are color coded wire leads. Sensor Voltage: 18 to 30 VDC, supplied from fire alarm control panel Sensor Current - 205 mA @ 24 VDC; supervisory and alarm Compatibility 4100ES/4010ES/4100U IDNet or MAPNET II addressable, communications, automatically selected. Loading - One address, one unit load per sensor. Electrical Terminations: Terminal blocks for 18 to 12 AWG Sensor Ambient: 14° F to 103° F (-10° C to 39° C) Sampled Air: -4° F to 140° F (-20° C to 60° C) Sensor Humidity: 10-95% RH, non-condensing Sampling Network - Maximum area of coverage = 8000 ft2, maximum pipe length in accordance with Vision Systems computer design tool (ASPIRE) and NFPA standards UL Listed Velocity Range: 0 to 4000 ft/min (0 to 1200 m/min) Alarm Sensitivity Range - 0.016% to 4.08%/ft obscuration, selected at the fire alarm control panel; NOTE: UL listed evacuation alarm sensitivity is not to be less sensitive than 0.625%/ft. Recognized Sensitivity Levels: Three levels, selectable and designated as required at the fire alarm control panel. Sensor Service Access -Internal DB-9, RS-232 connection for a service computer using VESDA, Vconfig Pro software program (authorized service access only) Enclosure Rating - NEMA 1 (IP 30)

default.send_request_amp_Group2