Prices  UG-5-AFR-24V-ST2  Calectro  United States

BRAND Calectro
Product UG-5-AFR-24V-ST2
Description air duct smoke switch 24 V AC/DC
Internal code IMP4622222
Custom code 85311030
Technical specification 24 V AC/DC The Uniguard smoke detector is designed to detect smoke in ventilation ducts and combines a smoke detector with an adapter system, the pipe and housing being specially designed for optimal air flow through the smoke detector.The UG-5 can be installed on each side of the duct in four different positions: 0°, 90°, 180° and 270°. Patented. Comes complete with air duct removal pipe, 0.6 m length Power supply: 24 V AC/DC -15%, +10% Smoke detector type: UG-5-AFR-24V optical Max current consumption: 220 mA Operating temperature: -10°C to +55°C Max Humidity: 99% RH Air speed range: 1 to 20 m/s Approvals: VdS G213014, CE, pren-54-27 Smoke alarm release via remote reset Relay output: Potential free Smoke alarm relay: Two changeover contacts 250 V, 8A Service alarm: One changeover contact 250 V, 5 A System fault alarm: One changeover contact 250 V, 5 A Air speed alarm: One switching contact 250 V, 5 A LED on smoke detector: Green: Service alarm (contamination) red - smoke alarm LED on printed circuit board: Green: normal operation yellow - system error yellow - air speed alarm Adapter housing: ABS Protection class: IP54

default.send_request_amp_Group2