Prices  RUT-4 OP  Arteche  United States

BRAND Arteche
Product RUT-4 OP
Description Power supply supervision relay
Internal code IMP3312554
Weight 0.25
Technical specification  Drop-out time: >150 ms  Contacts:  Permanent current: 10A  Instantaneous current:  30 A during 1s  80 A during 200 ms  200 A during 10 ms  Making capacity:  40A 0,5s 110Vdc  30A 1s 36Vdc 30.000 operations (1op/15seconds) Umax, opened contact: 250 Vdc/400 Vac  Mechanical life: 107 operations  Operating temperature: -10°C +55°C  Storage temperature: -30°C +70°C  Operating humidity: 93%/40°C

default.send_request_amp_Group2