Prices  RPF100+ TRV MultiRange L1000  Thermokon  United States

BRAND Thermokon
Product RPF100+ TRV MultiRange L1000
Internal code IMP4638464
Custom code 85365019
Technical specification Pendulum sensor temperature - 0..5 V, 0..10 V 8 measuring ranges can be set on the transmitter (standard: 0..+160 °C), temperature range: -35.. +70 °C Measuring insert with SI protection to protect against moisture and vibrations Output: 0..10 V = Power supply: 15..24 V = (±10%) or 24 V ~ (±10%) Sensor cable: LiYY, 2x0.25 mm², L=1000 mm, color white Sensor sleeve: stainless steel V2A, Ø=15 mm, installation length 100 mm, hexagonally pressed Impact and shatterproof housing USE-S with hinged cover (PC, pure white, IP65) Removable cable entry (MF20 flex, exchangeable) and removable plug-in terminal (max. 2.5 mm²) Potentiometer for calibrating offset values including mounting base and fastening screws

default.send_request_amp_Group2