BRAND | Thermokon |
Product | Art.-Nr. 659413 |
Description | Differential pressure sensor |
Internal code | IMP4619005 |
Custom code | 90262020 |
Technical specification | DPA250+ RS485 Modbus MultiRange Differential pressure measurement, Vol — Modbus, 0..5/10 V Output: RS485 Modbus & 2x 0.. 10 V = (differential pressure and volume flow) Measuring range differential pressure: 0.. +25 | 0.. +50 | 0.. +100 | 0.. +250 | -25.. +25 | -50.. +50 | -100.. +100 | -150.. +150 Pa (default: 0.. +250 Pa), adjustable on the device Volume flow measuring range: 0.. +750,000 m³/h, adjustable via Thermocon UseApp Measurement units: Pressure in Pa or inchWc, volume flow in m³/h or cfm Pressure accuracy: ±1 Pa at measuring range <250 Pa Power supply: 15.. 35 V = or 19.. 29 V ~ Impact and shatter-proof housing USE-L with hinged cover (PC, pure white, IP65) Removable cable entry (M25, replaceable) and removable plug terminal (max. 2.5 mm²), Output protection circuit (reverse polarity protected) Screw connection on level ground, prepared for latching installation on standard DIN rail TS35 (35x7.5 mm) incl. mounting base, fixing screws, 2 m PVC connection hose and pressure connection set |
default.send_request_amp_Group2