BRAND | Afriso |
Product | AFA 11 (40890) |
Description | Liquid detector |
Internal code | IMP4767936 |
Custom code | 90261029 |
Technical specification | For visual and acoustic reporting of liquids with a flash point > 55 °C. AFA 11 is suitable for the media heating oil, diesel fuel or low-viscosity lubricating oils, engine oils, transmission oils or hydraulic oils, vegetable and transformer oils, water and other liquids. Used as a class III leak detection system in accordance with EN 13160-1/-4. AFA 11 consists of a signal section with optical/acoustic alarm, Test/confirm button, relay output and optoelectronic probe. The The probe is installed at the lowest point in the area to be monitored. If the leaked liquid is detected, an alarm is triggered. The The acoustic alarm can be ended with the Acknowledge button. The optical The alarm persists until the leak is eliminated. About the Potential-free relay contact can additional external signal transmitters (e.g. ZAG 01 additional alarm device, horn) or a building management system be connected. Power failure alarm: A 9 V battery can optionally be connected so that an alarm sound is triggered in the event of a power failure (power failure). The Alarm cannot be acknowledged and ends when power returns. Box contents: signal unit and 1 optoelectronic probe (10m) Supply voltage: AC 100-230 V Output: 1 potential-free changeover contact Contact rating: AC 250V 2A Protection class (signal part): IP 30 Verification of usability: DIBt Z-65.40-214 |
default.send_request_amp_Group2