Prices  7ME5835-0AA00-0KN0 / TurboLux 3  Mecon  United States

BRAND Mecon
Product 7ME5835-0AA00-0KN0 / TurboLux 3
Internal code IMP5000400
Custom code 90261081
Technical specification Turbo-Lux 3 DN150 1250 GPM KIT Description: Turbo-Lux 3 workings Measurement principle: Diaphragm as differential pressure transmitter with bypass flow meter flow direction: arbitrary, taking into account the direction of the arrow Installation position: any Measurement accuracy Measurement deviation: ±2.0% of the end value of the measurement range (FM) ± 5.0% of measurement value (LPCB) ±2.5% of the final measurement range value (vDS) process conditions Nominal size: 6"/DN 150 (ø 168.3 mm) grooved Pump rated power: 1250 usGpm Inlet and outlet distance:5 x D and 2 x D Display range: 500 — 2500 usGPM 1900 - 9500 lpm Installation length: 200 mm (+0.0 mm/-3.0 mm) operating conditions Medium: water Operating temperature: +4 to +50 °C max. operating pressure: FM 500 psi (34.5 bar) LPCB/ VdS PN 16 (232 psi) Constructive structure Housing tube: painted steel with rolled groove Differential pressure collection tube: brass Floater: stainless steel Side flow valve: stainless steel Filter screen: stainless steel Filter screen: stainless steel Seal: NBR Certificates/Approvals FM LPCB VdS Measurement accuracy certificate (bypass meter): with

default.send_request_amp_Group2