BRAND | Thermokon |
Product | 626347 |
Internal code | IMP4890991 |
Custom code | 90258040 |
Technical specification | FTK+ 140 VV Duct sensor temperature, humidity — 0.. 5 V, 0.. 10 V Output voltage: 2x 0.. 10 V or 0.. 5 V, adjustable via jumper, min. load 10 kO Operating temperature range: -20.. +70 °C, temperature accuracy: ±0.3 K (typ. at 21 °C) in Standard measurement range, potentiometer for offset adjustment Humidity measurement range: 0..100% rH without condensation, 0.. 85 kJ/kg enthalpy, 0.. 50 | 0.. 80 g/m³ absolute Humidity, 0.. +50 | -20.. +80 °C dew point, adjustable on the transmitter Humidity accuracy: ± 2% between 10..90% rH (typ. at 21 °C), potentiometer for offset adjustment Power supply: 15.. 24 V = (± 10%) SELV, 24 V ~ (± 10%) SELV Connection: removable Flextherm M20 cable entry for cables with Ø=4.5.. 9 mm, detachable plug-in terminal, max. 2.5 mm² Material in contact with media: sensor tube, PA6, with stainless steel wire mesh filter, black, Ø=19.5 mm, Installation length: 140 mm, housing: USE-S, impact and shatterproof housing with hinged cover, PC, Colour: pure white, protection class: IP65 Box contents: including mounting flange, including mounting kit (screws and accessories) Notes: flow rate max. 12 m/s |