Prices  1101-31D2-0069-810  S+S REGELTECHNIK  United States

BRAND S+S REGELTECHNIK
Product 1101-31D2-0069-810
Description Duct/ smoke gas temperature measuring transducer
Internal code IMP4621494
Technical specification RGTM1-I 300MM KV Power consumption < 1.0 VA/ 24 V AC/ DC; < 0.55 VA/ 24 V DC Voltage supply 15...36 V DC depending on working resistance, residual ripple stabilised ± 0.3 V Working resistance máx. 750 Ohm/ 24 V DC Temperature deviation typically ± 0.2 K at +25 °C Sensor Pt1000, DIN EN 60751, class B, glass sensing resistor (Perfect Sensor Protection) Connection type 2- or 3-wire connection Measuring ranges multi-range switching with 8 switchable measuring ranges, see table (other ranges optional) with manual zero point correction (± 10 K) Ambient temperature Measuring transducer –30...+70 °C Process connection by mounting flange, stainless steel V2A (1.4305) (included in the scope of delivery) Protective tube stainless steel, 1.4571, V4A, Ø = 8 mm Electrical connection 0.2 - 1.5 mm², via push-in terminal Connecting head form B, material aluminium, colour white aluminium (similar to RAL 9006), M 20 x 1.5 Output 4...20 mA Permissible air humidity < 95 % r. H., non-precipitating air Protection class III (according to EN 60 730)