BRAND | Calectro |
Product | UG-5-AFR-24V-ST2 |
Description | air duct smoke switch 24 V AC/DC |
Internal code | ONR4742593 |
Custom code | 85311030 |
Technical specification | 24V AC/DC The Uniguard smoke detector was developed and combined to detect smoke in ventilation ducts a smoke detector with an adapter system, the pipe and housing specifically for optimal airflow were constructed by the smoke detector. The UG-5 can be used on each side of the channel in four different Positions are installed: 0°, 90°, 180° and 270°. Patented Complete delivery with air duct removal pipe, 0.6 m in length. Power supply: 24 V AC/DC -15%, +10% Smoke detector type: UG-5-AFR-24V optical Max. power consumption: 220 mA Operating temperature: -10°C to +55°C Max. humidity: 99% RH Air speed range: 1 to 20 m/s Approvals: VdS G213014, CE, prEN-54-27 Smoke alarm unlocking via remote reset Relay output: Potential-free Smoke alarm relay: Two 250 V, 8A switch contacts Service alarm: One changeover contact 250 V, 5 A System fault alarm: One changeover contact 250 V, 5 A Air speed alarm alarm: One switch contact 250 V, 5 A LED on smoke detector: Green: service alarm (contamination) Red smoke alarm LED on circuit board: Green: normal operation Yellow - system error Yellow - air speed alert Adapter housing: ABS Protection class: IP54 |
Press on flag images to see contact information!