BRAND | Jaquet |
Product | SpeedSys 200 Overspeed Detection module |
Internal code | ONR4658193 |
Technical specification | SSY200-000-002 Description: Overspeed detection system for SIL applications, 1 channel module Brand: Istec Item: SpeedSys 200 Key features: Speed, overspeed and acceleration Suitable for 1oo1, 1oo2 or 2oo3 voting configurations 8ms system reaction time Advanced self-monitoring and diagnostics SIL 2 (IEC61508) certified protection Suitable for API 670 compliant applications Suitable for passive, active and proximity sensor with Ex-ia certified inputs (IECEx zone 0.1.2) DIN rail system, 24 VDC Hazardous areas: Type of protection: Ex ia; intrinsic safety on sensor inputs Approval marking: Ex II (1) G [Ex ia Ga] IIC (gas) . Ex II (1) D [Ex ia Da] IIIC (Dust) Identifiers: IECEx IBE 20.0045 . ibexu20ATEX1157 Important information: Certification refers to sensor input only. Refer to the Certificates for Specific Parameters of the Mode of operation and special conditions of use. |
Press on flag images to see contact information!