BRAND | AEG |
Product | Protect 8.33 |
Internal code | ONR4717715 |
Technical specification | a) Rectifier: Supply voltage: 400 V 15%/3 Ph./PE (adjustable to 3x380 V or 3x 415 V) Power consumption at rated load: 98 A at 400 V Power consumption at rated load and battery charge: 123 A at 400 V Network effects: 6-pulse+ filter Frequency: 50 Hz 10% or 60 Hz 10% DC output voltage: 384 V 20% b) Inverter: Nominal output: 60 kVA (at cos = 0.8 ind.) AC output voltage: 400 V/3 Ph./N/PE Variance, static: 1% Deviation, dynamic: < 2% (in case of load surge 0 - 100% - 0 without network assistance) Frequency: 50 Hz, optional 60 Hz Power factor range: 0 ind. - 1 - 0 kap. Output phase current: 87 A at 400 V Voltage curve shape: sinusoidal Distortion factor: < 3% in total DC voltage, Load and power factor range Non-linear load: up to 100% of the rated UPS capacity Short circuit current L-N 500 ms 3.22 x Inenn Short circuit current 3-phase 500 ms 1.81 x Innn Crest factor: 3, distortion factor where < 3% Overload behavior: 150% for 1 min., 125% for 10 min. c) General data: Supply voltage (EUE): 400 V 10% (adjustable)/3 Ph./N/PE overall efficiency 100% load (PF=0.8): 91.9 ± 2% Radio suppression degree: “A” in accordance with EN 62040-2 Immunity: according to EN 61006-4 Cooling type: reinforced air self-cooling with built-in redundant fans Operating mode: continuous operation Painting: RAL 7035 (powder coating) Protection class: IP20 Dimensions (WxHxD): 750 mm x 1800 mm x 860 mm |