BRAND | Alerton |
Product | AXM-10-4-8 |
Description | Expansion Module |
Internal code | ONR4941391 |
Technical specification | Expansion Module for the ACM Power - Unit requires 24 VAC, 50- 60 Hz, 20 VA minimum. Half-wave rectified. Output loads powered separately. 10 Inputs - Jumper-selectable, 12- bit universal inputs accept thermistor, dry contact, 0-5VDC, 4-20 mA, or 0-10 VDC signals. Inputs 1, 2, and 3 support pulsed inputs with 10 msec minimum pulse length. No external resistor is required for 4- 20 mA. 04 Binary Outputs - Binary outputs rated 24 VAC @ 0.5 A with Hand-Off-Auto (H-O-A) switches for manual override. H-OA status can be monitored in software. Power source isolated from AXM power. 08 Analog Outputs - Analog outputs are driven by precision D/A converter. DIP-switch configurable to provide 0-10 VDC or 0-20 mA. Each analog output has an H-O-A switch and potentiometer for manual override. H-O-A and potentiometer status can be monitored in software. Max Dimensions - 6.95” (176.5 mm) H X 4.95” (125.7 mm) W X 1.6“ (40.5 mm) D. Terminations - Removable header-type screw terminals simplify field wiring Environmental - 32-131°F (0-55° C). 0-95% RH, non-condensing Communications - Twisted-pair, multi-drop AXM communications bus to ACM base unit. |