BRAND | Klinger Born |
Product | 8503.4040 |
Description | Star Delta Timer |
Internal code | ONR3899265 |
Technical specification | Nominal frequency 50-60Hz Voltage range 85-110% Rated power 2VA Ambient temperature -10 ° C ... + 55 ° C Control input K1 Same potential as input L3 Star-delta time domain 0.15 sec ... 30 sec Switchover time star-delta Approx. 60ms Way of working Controller controlled with watch dog B10 (B10d) 400,000 (800,000) Max. Cross section 2.5mm² Attachment On DIN standard rails (EN60715) Dimensions of housing 45.5 x 74 x 85mm (WxHxD) Technical information Wiring diagram 230V DIN rail housing 10-pin Relay outputs nominal voltage 250V AC Continuous current 5A Inrush current 5A Rated switching capacity 1250VA Contact material AgSnO Mechanical life 50x10 6 switching cycles Electrical life at 5A / 250V AC 100x10 3 switching cycles Max. Switching frequency at nominal load 360 switching cycles / h Response time / fall time 10 / 10ms Test voltage contact coil 4000V ACeff Test voltage open contact 750V ACeff Installation position Any Vibration resistance (30 ... 500Hz) G> 4 Shock resistance 11ms G> 10 |